Scenario details:

  • We have a Modbus RTU PLC. This PLC has in its internal memory a series of variables / registers (for example, a temperature and 3 counters, …) which must be read and periodically sent to an MQTT broker
  • Therefore, the MTX-Tunnel must periodically interrogate the PLC through a serial port every 15 minutes to read these registers. The registers to be read are: for the temperature register nº20, and the counters are in registers 21, 22 and 23 respectively
  • The MTX-Tunnel must send the value of the registers after each reading to an MQTT broker using a JSON object, but it must be able, in case of 2g / 3g / 4g communications failure, to store in flash memory up to 1500 readings that it will send when communications are restored
  • For more security in communications, the modem must have DUAL SIM. In other words, the modem must have 2 SIM cards from 2 different telephone operators. The modem will need to change SIMs as long as it cannot get an IP address for more than 120 seconds

Solution: MTX-Tunnel firmware + MTX-IOT-S [4-N]

Config.txt configuration file:

Configuration Observations
COMM2_baudrate: 9600
COMM2_bitsperchar: 8
COMM2_autorts: off
COMM2_autocts: off COMM2_stopbits: 1
COMM2_parity: none
GPRS_apn: movistar.es
GPRS_login: MOVISTAR
GPRS_password: MOVISTAR
GPRS_apn2: airtelnet.es
GPRS_login2: vodafone           
GPRS_password2: vodafone
GPRS_timeout: 0
MTX_PIN: 0000
MTX_mode: none
MTX_model: 199802407
MTX_portAux: modbusmaster
MTX_TPProtocol: ntp
MTX_TPServer: ntp.roa.es
MTX_TPServer2: es.pool.ntp.org
MTX_ping: 35
MTX_pingIP: 8.8.8.8
MTX_rssiLevel: 10
SMS_allPhones: on
SMS_sendIP: on
SMS_ATEnabled: on
SMS_ATResponse: on
FIREWALL_enabled: off
LOGGER_enabled: on
LOGGER_mode: mqtt
LOGGER_mqttTopic: /LOGGER
LOGGER_registerSize: 300
LOGGER_numRegistersFlash: 1500
MODBUS_address: 1
MODBUS_start: 20
MODBUS_numwords: 4
MODBUS_period: 900
MODBUS_readCommand: 3
DUALSIM_select: dual
DUALSIM_mode: ip
DUALSIM_timeout: 120
MQTT_enabled: on
MQTT_server: tcp://test.mosquitto.org:1883
MQTT_id: [IMEI]
MQTT_login:
MQTT_password:
MQTT_attopic1: [IMEI]/AT
MQTT_atrtopic: [IMEI]/ATR
MQTT_qos: 1
MQTT_keepalive: 60
Serial port baud rate
Number of bits
No flow control
No flow control
1 stop bit
No parity
APN GPRS from your network operator
GPRS Login
GPRS Password
GSM operator GPRS APN. Secondary SIM
GSM operator GPRS login. Secondary SIM
GSM operator GPRS password. Secondary SIM
Modem is always GPRS connected
SIM Card PIN
MTX-Tunnel mode
MTX modem model
AUXILIAR COM port used as master modbus
Time synch. protocol
Time server
Backup time server
Ping every 35 minutes without comms
IP address to ping
We activate the coverage LED
All phone numbers are authorized
IP sent to phone which called or “on” SM Remote
AT commands by SMS enabled
Modem response to AT command with SMS
Any IP will be able to connect to the modem
We enable the MTX Logger, to store the records
Shipping mode by MQTT
Sending topic to MQTT broker to send counter data
Register size
Maximum number of records in MTX
ModBus addresses of devices to be read
Initial addresses of each device
Number of records read from each device
Frequency of readings in seconds
Read command
DUAL SIM mode activated with external initial SIM
SIM change mode
Timeout for SIM change in case of problems
MQTT service enabled
Broker IP/DNS specified, including identifying port
Identifier
Username
Password
MQTT topic to send AT commands
Topic to send replies to commands to
QoS established
Connection keep alive (60 seconds)  

Details:

  • In this example a modem is used using the RS485 port, but the RS232 port could be used without problems (to use the RS232 port the parameter MTX_invertedCom: on should be entered)
  • The summary of this example is as follows: the modem periodically reads, every 15 minutes, a series of ModBus registers from the PLC and sends them via a JSON object to an MQTT broker (to the topic specified in the LOGGER_mqttTopic parameter). In case of not being able to send the record (because there is no coverage at that time or the server is down) it stores the data in memory to send them later. Using MQTT commands it is also possible to connect to the equipment directly and consult / change the PLC registers in real time (to do this, search in this manual for the commands AT ^ MTXTunnel = getmodbus and AT ^ MTXTUNNEL = setmodbus)
  • The JSON object sent to the MQTT broker is encoded as follows, as an example:
    {“IMEI”:353234028103206,”P”:”ID00001”,”TYPE”:”MODB”,”A”:1,”TS”:”20/08/12 08:31:44”,”ST”:20,”V1”:23,”V2”:275,”V3”:274,”V4”:32765}
  • The modem has DUAL SIM (DUALSIM_mode: dual) configured. This will cause the modem to boot using the primary SIM card, which in the case of the MTX-IOT-S [4-N] modem is the external SIM card. In case coverage is lost and it is not possible to register on the operator network for 60 seconds (DUALSIM_timeout), the modem will switch to the secondary SIM card